联系人:孔敏冲 (小姐)
手机:
电话:
传真:
邮箱:melody.kong@email.acrel.cn
地址:江苏省江阴市南闸东盟路5号
General
PZ series intelligent DC energy meter is designed for applications such as DC panels, solar power, telecommunications base stations, and charging posts. This series of instruments can measure voltage, current, power, forward and reverse power in DC system. It can be used for local display, and connected with industrial control equipment, computers, form a measurement and control system. And it has a variety of external excuse functions for the user to choose.
Parameters
Accuracy Class 0.5
Frequency 50/60Hz
Power Supply 85~265VAC/DC,20~60VDC,100~350VDC
Power consumption ≤2W
Input voltage 0~100V,0~500V,0~1000V |
|
|
Dimension(L*W*H) 75*75*98mm
Installation DIN 35 mm
Input resistance ≥6kΩ/V
DI/DO 2DI/2DO |
Technical Parameters
Input |
DC voltage |
Input range |
Direct access:0~100V, 0~500V, 0~1000V |
Input?resistance |
≥6kΩ/V |
||
DC current |
Input range |
Indirect access:0-2500A |
|
Shunt |
75mV |
||
Hall Current Sensor |
0~20mA, 0~5V |
||
Power consumption |
≤1mW |
||
Overload |
1.2 times (normal), 2 times/second (continued) |
||
Accuracy class |
Class?0.5 |
||
Pulse constant |
750V、300A; 1000V、300A; 1000V、200A; Default pulse constant: 100imp/kWh |
||
Function |
Measuring |
Voltage、Current、Power |
|
Calculate |
Current total electricity, Current positive energy, Current reverse power |
||
DI、DO |
PZ72: 2DO+2DI ; PZ96:2DO+4DI |
||
Display |
LCD(the backlight delay time can be adjusted) or LED |
||
Communication |
RS485,?Modbus-RTU / DL / T645-07, Band :1200/2400/4800/9600,?infrared:1200 |
||
Power Supply |
Voltage range |
85~265VAC?/?DC、50/60Hz; 20~60VDC; 100~350VDC |
|
Power?consumption |
≤?2W |
||
Insulation resistance |
≥?100M Ω |
||
Power frequency withstand voltage |
3kV/1min (RMS) |
||
Environment |
Temperature |
Normal operating temperature: -25 °C ~ +60?°C; Storage temperature: -20℃~+70℃ |
|
Humidity |
≤93%RH, no condensation, no corrosive gases |
||
Altitude |
≤2500m |
Display
Network